With the UAK it is possible to make a safe and simple fused voltage branch in your distribution system.
Description
53 Recent ViewsCall for more details
The UAK series of insulated busbar terminals let you connect your instruments to live busbars. A fuse holder is an integrated part of this terminal, proving you with protection at the source. The terminal can be installed directly onto the busbar using an insulated Allen key driver. This makes the installation of this unique product a one handed exercise. The UAK can be used for temporary or permanent voltage measurements.
The fuse holder is mounted directly on the metal that makes contact with the busbar, thereby providing a secure connection with a high short circuit rating. For connection to the Netural bar, the model UAK16 provides an unfused connection
Technical specifications
Maximum voltage: 690V Test voltage / spike: 3kV/50Hz 6kV Max current: 10A Isolation class: E (max120°) Fuse type: 5x25mm (with indicator) 10A SIBA DIN41576-2 Short circuit rating: 70kA@400V/50Hz IP rating: IP20 Ambient temperature: –5...+40°C (1) Temperature rise busbar: Max. 75K (1)
Busbar connection: Via Allen key bolt M8 Allen key size: Number 6 Busbar thickness: Max 15mm/Min 4mm Housing: Polyamide (PA6.6) Material terminal: Nickel plated brass Clapsing on Rail: Allen bolt M8, Allen key no. 6, tightening torque. 6Nm, max. 8Nm
1) Maximum temperature of the busbar: 120ºC(Sum of the busbar temperature rise and the ambient temperature) KEMA certified, IEC60947-7-3
To contact SmarterCTRL (by Industrial Automation Group) about ELEQ UAK - Easy Voltage Tap for Busbar use Get a quote.
The UAK series of insulated busbar terminals let you connect your instruments to live busbars. A fuse holder is an integrated part of this terminal, proving you with protection at the source. The terminal can be installed directly onto the busbar using an insulated Allen key driver. This makes the installation of this unique product a one handed exercise. The UAK can be used for temporary or permanent voltage measurements.
The fuse holder is mounted directly on the metal that makes contact with the busbar, thereby providing a secure connection with a high short circuit rating. For connection to the Netural bar, the model UAK16 provides an unfused connection
Technical specifications
Maximum voltage: 690V Test voltage / spike: 3kV/50Hz 6kV Max current: 10A Isolation class: E (max120°) Fuse type: 5x25mm (with indicator) 10A SIBA DIN41576-2 Short circuit rating: 70kA@400V/50Hz IP rating: IP20 Ambient temperature: –5...+40°C (1) Temperature rise busbar: Max. 75K (1)
Busbar connection: Via Allen key bolt M8 Allen key size: Number 6 Busbar thickness: Max 15mm/Min 4mm Housing: Polyamide (PA6.6) Material terminal: Nickel plated brass Clapsing on Rail: Allen bolt M8, Allen key no. 6, tightening torque. 6Nm, max. 8Nm
1) Maximum temperature of the busbar: 120ºC(Sum of the busbar temperature rise and the ambient temperature) KEMA certified, IEC60947-7-3